Bitmain ANTSPACE HK3 Cooling Container
The Bitmain Antspace HK3 Liquid Cooling Container revolutionizes cooling solutions tailored for cryptocurrency mining operations, especially for rigs employing Bitmain Antminer ASIC hardware.
Cryptocurrency mining, notably for flagship currencies like Bitcoin, demands substantial computational power, resulting in significant heat generation. Conventional cooling methodologies often struggle to maintain optimal operating temperatures, risking diminished performance and hardware impairment.
To tackle this challenge, Bitmain conceived the Antspace HK3 Liquid Cooling Container. This containerized cooling system integrates liquid cooling technology to efficiently dissipate heat produced by mining rigs. Liquid cooling offers superior cooling efficiency compared to traditional air cooling methods. You can also order the hammer d10 5g ltc doge miner
Engineered to accommodate multiple Bitmain Antminer ASIC mining rigs, the container provides a centralized and scalable cooling solution. The liquid cooling system circulates coolant through a network of pipes or channels, engaging with heat-generating rig components. As the coolant absorbs heat, it’s channeled away from the rigs to a heat exchanger, where heat disperses into the surroundings.
The Antspace HK3 Liquid Cooling Container boasts several advantages over air cooling solutions. It sustains stable, optimal operating temperatures, enhancing mining performance and equipment longevity. Moreover, it mitigates noise emissions from mining equipment, rendering it suitable for diverse deployment environments.
Product Specification: Bitmain ANTSPACE HK3 Cooling Container
- Model: ANTSPACE HK3
- Dimensions (LWH) (mm): 605824382896
- Miner Capacity: 210 units -S19 Hyd. Series miner
- Operating Power(kW): 1047~1050
- PUE (Power Usage Effectiveness): 1.022 (Excluding cooling tower)/1.036 (Including cooling tower)
- Input Voltage and Frequency:
- 415V±5% 60Hz (North America)
- 400V±5% 50Hz (EU, Middle East)
- Detailed Characteristics:
- Shipping Weight (T): 8
- Operating Weight (T): 12
- Main Switch of Power Distribution Cabinets (A):
- 1200 (North America)
- 1250 (EU, Middle East)
- Rated Current (A): 952
- Standard Power (kW): 1049
- Maximum Power (kW): 1050
- Rated Current per Miner (A): 10
- Inlet Cable: Requirements per phase:
- L1 single core cable 600kcMil(300mm²)x4
- L2 single core cable 600kcMil(300mm²)x4
- L3 single core cable 600kcMil(300mm²)x4
- N Single-core cable 600kcMil(300mm²)x4
- PE single-core cable 500kcMil(240mm²)x2
- Connection Interface (Cooling Tower): DN125(GB/T 9119-2010 PN16 DN125)
- Connection Interface (Plate Heat Exchange Interface): DN100(GB/T 9119-2010 PN16 DN100)
- Flow Rate (m³/h): >85
- Quantity of ANTSPACE powered by one 2500kVA Transformer: 2
Specification Details For Dry-Wet Towers
Choose between two options based on personalized demand:
- Dry-Wet Tower Traditional Type (DWT-T):
- Dimensions (LWH) (mm): 580022404200
- Heat Dissipation Capacity (kW): 1000
- Operating Power (kW): 14~28
- Dry-Wet Tower Container Type (DWT-C):
- Dimensions (LWH) (mm): 605824382896
- Heat Dissipation Capacity (kW): 1000
- Operating Power (kW): 14~28
Environmental Requirements: Bitmain ANTSPACE HK3 Cooling Container
- The cooling tower must be placed on flat ground with a horizontal degree (±1 degree).
- The ground surface should be hardened and stable, capable of withstanding at least a 14-ton load.
- A 10-ton crane is necessary for unloading ANTSPACE and the cooling tower.
- Additional items such as stairs, transformers, cables, bridge racks, and cable distribution boxes are not included in ANTSPACE delivery. The BITMAIN team can offer design suggestions if required.
- Clients must confirm the container’s opening direction to face air-intake. The left door is the current default design.
- Maintain at least 2 meters of air intake space around the cooling tower.
- Altitude: ≤3000m. If above 1000 meters, derate the transformer and switch; decrease the total power of ANTSPACE by 1% per 100-meter elevation increment.
- Operating temperature: -25°C to 40°C. Operating humidity: 10%RH to 90%RH. When initial coolant temperature is below 20°C, activate internal circulation to heat coolant to above 20°C before starting mining machines.
- When ambient temperature is below 5°C, switch cooling tower to cold-dry mode.
- Select pure water or suitable antifreeze as coolant based on local climate conditions.
- Suitable ambient temperature for ANTSPACE does not indicate suitable ambient temperature for mining machines.